Concrete Mix Design UK 2026 | BS 8500 & Eurocode 2 Calculator

Concrete Mix Design UK

BS 8500 & Eurocode 2 Compliant Mix Design Calculator – Updated 2026

Concrete Mix Design Calculator – BS 8500 / EC2 2026

Select your application, exposure class, and design parameters to generate a BS 8500-compliant concrete mix design with Eurocode 2 compliance checks. The calculator outputs strength class, maximum w/c ratio, minimum cement content, aggregate quantities per m³, and a full compliance summary against BS 8500-1 Table A.1 limiting values.

Concrete Mix Design Output – BS 8500 / EC2 Compliant:

BS 8500 Compliance Summary:
Recommended Designated Mix:
BS 8500-1 designated mix for your exposure class and application
Minimum Strength Class (EC2):
Characteristic cylinder / cube strength fck/fck,cube at 28 days
Maximum Water / Cement Ratio:
BS 8500-1 Table A.1 limiting w/c ratio for your exposure class and design life
Minimum Cement Content: kg/m³
BS 8500-1 Table A.1 minimum binder content for your exposure class
Recommended Cement Content (designed): kg/m³
Designed content meeting all limiting values with appropriate margin
Free Water Content: litres/m³
Based on target w/c ratio, aggregate size, and consistence class; adjust for aggregate moisture
Total Aggregate Content: kg/m³
Combined fine and coarse aggregate to fill remaining volume
Fine Aggregate (sharp sand): kg/m³
Sharp / concreting sand; target ~38–42% of total aggregate by mass
Coarse Aggregate: kg/m³ ( nominal max size)
Crushed stone or gravel; ~58–62% of total aggregate by mass
Nominal Cover to Reinforcement (EC2): mm
cnom = cmin + Δcdev (10mm allowance); Structural Class S4, 50-year design life. Adjust for actual structural class.
Air Entrainment Required:
Required for XF3 and XF4 freeze-thaw exposure; target 4–6% entrained air content
Cement Type Recommendation:
Based on your exposure and sulphate class; confirm with BS 8500-1 Table A.1
Total Volume to Order (incl. % wastage): m³
Recommended order volume
Total Quantities for This Pour:
Ready-Mix Cost Estimate: £
Based on 2026 average UK ready-mix prices for this mix class in South East England; excludes delivery surcharges and pump hire

Concrete Mix Design to BS 8500 and Eurocode 2 – UK Guide 2026

Concrete mix design is the process of selecting the right proportions of cement (binder), water, fine aggregate (sand), and coarse aggregate to produce concrete that meets the required strength, durability, workability, and other performance criteria for a specific application. In the UK in 2026, concrete mix design for structural applications is governed by BS EN 206:2013+A2:2021 (the European concrete specification standard) and its complementary British Standard BS 8500-1:2015+A2:2019 and BS 8500-2:2015+A2:2019. Structural design that specifies the concrete strength and durability requirements is carried out under BS EN 1992-1-1 (Eurocode 2) and its UK National Annex.

The BS 8500 standard provides two routes to specifying concrete. The first is the designated mix route — specifying a named mix (e.g. GEN1, RC30, PAV1) whose composition, performance, and constituent materials are pre-defined in BS 8500-2. This is the most common route for domestic and light commercial work. The second is the designed mix route — specifying performance requirements (strength class, exposure class, maximum w/c ratio, minimum cement content) and requiring the concrete producer to design a mix that meets them. This is the standard route for engineered structural concrete. The calculator on this page supports the designed mix approach, providing BS 8500-1 Table A.1 limiting values for your chosen exposure class.

The most critical concept in concrete mix design is the relationship between the water/cement (w/c) ratio and both strength and durability. Reducing the w/c ratio simultaneously increases compressive strength and reduces porosity — making the concrete more resistant to all forms of chemical and physical attack. BS 8500-1 Table A.1 sets maximum w/c ratios and minimum cement contents for each exposure class to ensure adequate durability regardless of the structural design strength requirement. A concrete mix must satisfy all limiting values — sometimes the durability requirements are more demanding than the structural strength requirements, in which case the durability limits govern.

Exposure Classes – BS EN 206 and EC2

The BS EN 206 / Eurocode 2 exposure classification system categorises the chemical and physical environments to which concrete is exposed. Each exposure class leads to specific minimum requirements for concrete composition:

  • X0 — No risk of corrosion or attack. For unreinforced concrete in very dry environments only. Minimum strength C12/15. Not applicable to RC.
  • XC classes (XC1–XC4) — Corrosion induced by carbonation. The most common exposure class for UK RC construction. XC1 for dry interior slabs; XC4 for fully exposed external concrete subject to rain and drying.
  • XD classes (XD1–XD3) — Corrosion induced by chlorides other than seawater (de-icing salts). XD3 for car park decks, bridge decks directly exposed to de-icing salts — requires high-quality, low-permeability concrete (typically C40/50 or better).
  • XS classes (XS1–XS3) — Corrosion induced by chlorides from seawater. XS3 for intertidal/splash zone structures — the most severe corrosion environment.
  • XF classes (XF1–XF4) — Freeze-thaw attack. XF1 for moderate exposure (vertical surfaces in frost areas); XF4 for road and bridge slabs exposed to de-icing agents — requires air-entrained concrete.
  • XA classes (XA1–XA3) — Chemical attack. Relevant where concrete contacts sulphate-bearing soils or groundwater; requires sulphate-resisting cement (SRPC or combinations).

The Water/Cement Ratio – Why It Matters

The water/cement (w/c) ratio is the single most important parameter in concrete mix design. It directly controls two critical properties:

  • Compressive strength: The relationship between w/c ratio and strength follows Abrams' Law — lower w/c ratios produce higher strength. A w/c ratio of 0.45 typically yields C30/37 or better with CEM I cement; 0.60 yields approximately C20/25. Every 0.05 increase in w/c ratio reduces 28-day strength by approximately 5–8 N/mm².
  • Durability / permeability: A lower w/c ratio produces a denser, less permeable cement paste matrix, reducing the rate of ingress of water, carbon dioxide, chlorides, and sulphates. This is why BS 8500-1 Table A.1 specifies maximum w/c ratios for each exposure class — to ensure the concrete's pore structure is tight enough to protect embedded reinforcement and resist chemical attack over the design life.

BS 8500-1 Table A.1 – Limiting Values by Exposure Class (Summary)

The table below summarises the key limiting values from BS 8500-1:2015+A2:2019 Table A.1 for a 50-year design life and Structural Class S4 (standard). Values apply to CEM I cement; use of supplementary cementitious materials (GGBS, fly ash, silica fume) may allow relaxation of some limits — refer to BS 8500-1 Table A.1 notes for equivalence factors.

Exposure Class Description Min. Strength Class Max. w/c Ratio Min. Cement (kg/m³) Nominal Cover cnom (mm) Designated Mix Equiv.
X0No risk – very dry, unreinforced onlyC12/150.70260—GEN0
XC1Dry / permanently wet (internal RC)C20/250.7026025RC25 / GEN3
XC2Wet, rarely dry (foundations, buried)C25/300.6528035RC25 / FND2
XC3Moderate humidity / sheltered externalC28/350.6028035RC30
XC4Cyclic wet/dry – exposed externalC30/370.5530040RC30
XD1Chlorides – moderate humidityC32/400.5530040RC32 / designed
XD2Chlorides – wet, rarely dryC35/450.5032040Designed mix
XD3Chlorides – cyclic wet/dry (car parks)C40/500.4534045Designed mix
XS1Airborne sea saltC30/370.5030040Designed mix
XS2Submerged in seawaterC35/450.4532045Designed mix
XS3Tidal / splash / spray zoneC40/500.4034050Designed mix
XF1Freeze-thaw – moderate saturationC28/350.6028035RC30
XF3Freeze-thaw – high saturationC30/370.5530035Air-entrained RC30
XF4Freeze-thaw + de-icing saltsC32/400.4532040PAV1 / air-entrained
XA1Slightly aggressive chemistryC30/370.5530035FND2 (SRPC)
XA2Moderately aggressive chemistryC32/400.5032040FND3 (SRPC)
XA3Highly aggressive chemistryC35/450.4536050FND4 / designed

All values are for CEM I cement, Structural Class S4, 50-year design life, maximum aggregate size 20mm. Nominal cover includes a construction tolerance allowance Δcdev of 10mm. Refer to the full BS 8500-1:2015+A2:2019 Table A.1 for all notes, relaxations, and supplementary binder equivalence factors. This table is a summary for guidance only.

Structural Class Adjustments to Minimum Cover (EC2 UK NA)

Condition Structural Class Adjustment Effect on cmin
Design working life 100 years (instead of 50)+2 classes (e.g. S4 → S6)+10mm cover
Design working life 25 years (instead of 50)–1 class (S4 → S3)–5mm cover
Concrete strength ≥ C30/37 (for XC exposure)–1 class–5mm cover
Concrete strength ≥ C35/45 (for XD/XS exposure)–1 class–5mm cover
Slab element (vs beam/column)–1 class–5mm cover
Special quality control (monitored production)–1 class–5mm cover
Additional protection (stainless steel, coating)VariableReduce as agreed

Mix Design Reference Tables – Free Water Content and Aggregate Proportions

Approximate Free Water Content (litres/m³) by Consistence and Aggregate Size

Based on BRE / CIBSE mix design method for uncrushed (rounded) aggregates with CEM I cement. Crushed aggregate requires approximately 10–20 litres/m³ more water for equivalent consistence.

Consistence Class Slump (mm) 10mm Agg. 20mm Agg. 40mm Agg.
S1 (stiff)10–40175155140
S2 (medium)50–90195170155
S3 (high)100–150215190175
S4 (very high)160–210235210195

Proportion of Fine Aggregate (% of Total Aggregate) by w/c Ratio and Aggregate Size

For zone 2 sand (medium grading, most common UK sharp sand). Adjust ±5% for coarser (zone 1) or finer (zone 3) sand.

w/c Ratio 10mm Max Agg. 20mm Max Agg. 40mm Max Agg.
0.4047%38%32%
0.4549%40%34%
0.5051%42%36%
0.5553%44%38%
0.6054%45%39%
0.6556%47%41%
0.7057%48%42%

Strength vs w/c Ratio – CEM I (OPC) at 28 Days

w/c Ratio Approx. fck,cube (N/mm²) at 28 days Strength Class Designated Mix Equivalent
0.3565–70C55/67High-strength designed mix
0.4055–62C45/55–C50/60Designed mix (RC45+)
0.4548–55C40/50RC40 / designed
0.5040–48C35/45RC35 / designed
0.5533–40C28/35–C30/37RC30
0.6027–33C20/25–C25/30GEN3 / RC25
0.6522–27C16/20–C20/25GEN2 / RC20
0.7017–22C12/15–C16/20GEN1 / GEN2

Ready-Mix Concrete Prices by Strength Class – UK 2026

Strength Class Designated Mix Price/m³ (SE England, excl. VAT) Typical Min. Order Notes
C10/12GEN0£88–£1124–6 m³Blinding, fill only
C15/20GEN1£98–£1224–6 m³Strip foundations, trench fill
C20/25GEN2 / GEN3£106–£1304–6 m³Slabs, paths, garage floors
C25/30RC25£112–£1384–6 m³Lightly loaded RC
C30/37RC30 / PAV1£118–£1454–6 m³Standard RC, driveways – most common structural mix
C35/45RC35£124–£1524–6 m³Heavily loaded RC
C40/50RC40£132–£1624–6 m³Car park decks, aggressive exposure
C45/55+Designed mix£145–£200+4–6 m³High-strength structural concrete
Any gradeVolumetric / mini-mix£128–£175No minimumSmall volumes; on-site mixing

Essential Facts – Concrete Mix Design to BS 8500 and EC2

BS 8500 vs BS EN 206

In the UK, concrete is specified using BS 8500-1 and BS 8500-2 as complements to BS EN 206. BS EN 206 sets the European framework; BS 8500 provides UK-specific guidance on designated mixes, exposure class limiting values (Table A.1), and constituent material requirements. Any concrete used in UK structural work must comply with both BS EN 206 and BS 8500.

Designated vs Designed Mixes

Designated mixes (GEN0–GEN3, RC25–RC40, PAV1–PAV2, FND2–FND4) are pre-defined mixes with compositions fixed in BS 8500-2 — the specifier names the mix and the producer is responsible for compliance. Designed mixes specify performance requirements (strength class, exposure class, w/c ratio) and the producer designs the specific proportions. Designed mixes are required for all demanding structural applications.

Characteristic Strength and Target Mean

The characteristic strength fck is the value below which only 5% of test results are expected to fall. The concrete producer must target a higher mean strength (target mean strength = fck + 1.64σ) to allow for production variability. For ready-mix concrete with good process control, σ ≈ 4–6 N/mm². This means a C30/37 mix (fck,cube = 37 N/mm²) is typically designed to a target mean of approximately 47–47 N/mm².

Supplementary Cementitious Materials (SCMs)

Partial replacement of Portland cement with GGBS (ground granulated blast-furnace slag), fly ash (PFA), or silica fume can improve durability and reduce heat of hydration. BS 8500-1 allows up to 50% GGBS or 35% fly ash replacement by mass. SCMs generally improve long-term strength gain but reduce early strength — important for construction programme planning and striking formwork.

Air Entrainment for Freeze-Thaw

Concrete exposed to freeze-thaw cycling (XF3, XF4 exposure classes) must be air entrained — a chemical admixture introduces microscopic air bubbles (4–6% by volume) into the cement paste. These bubbles provide pressure relief for the expansion of freezing water, dramatically increasing frost durability. Air entrainment reduces strength by approximately 5 N/mm² per 1% air — the mix design must compensate with a lower w/c ratio or higher cement content.

Sulphate Attack and SRPC

Sulphates in groundwater and soils react with the tricalcium aluminate (C3A) in Portland cement to form expansive ettringite, causing cracking and disintegration. Where ground investigation confirms sulphate exposure (DS-2 or above), sulphate-resisting Portland cement (SRPC, CEM I-SR) or combinations with GGBS must be specified. BS 8500-1 designates FND2–FND5 mixes for increasing levels of sulphate aggressiveness.

Alkali-Silica Reaction (ASR)

Alkali-Silica Reaction (ASR) — also called concrete cancer — occurs when reactive silica in some aggregates reacts with alkalis in the cement paste in the presence of moisture, producing an expansive gel that causes map cracking and surface spalling. UK guidance (BRE Digest 330) and BS 8500-2 provide requirements for ASR prevention, including limits on alkali content of the cement and the use of reactive aggregates. Using GGBS or fly ash significantly reduces ASR risk.

Compressive Strength Testing (BS EN 12390)

Concrete compressive strength is measured in the UK by crushing 150mm cubes at 28 days to BS EN 12390-3. The strength class notation C30/37 refers to the characteristic cylinder strength / characteristic cube strength — 30 N/mm² cylinder and 37 N/mm² cube. The cube is approximately 25% stronger than an equivalent cylinder due to end restraint effects. UK structural design to EC2 uses cylinder strength; cube tests are used for conformity assessment.

Consistence and Workability

Workability is specified using the consistence class system (S1–S4 for slump; F1–F6 for flow). S2 (50–90mm slump) is the standard class for most site-poured concrete. S3 (100–150mm) is specified for pumped concrete or congested reinforcement. Self-compacting concrete (SCC) uses flow class F4–F6 and does not require mechanical vibration — useful for precast elements and densely reinforced sections. Higher workability increases water demand, requiring higher cement content to maintain the w/c ratio.

Curing Requirements

Proper curing is essential for achieving the design strength and durability. EC2 specifies minimum curing periods depending on cement type and temperature. For CEM I cement at 20°C, minimum curing under BS 8110 guidance was 3 days; EC2 requires a minimum curing time based on the maturity concept. In practice, UK specifications typically require 7 days of curing for normal concrete in XC3/XC4 exposure. Curing methods include water curing (ponding, spraying), membrane curing compounds, and insulating blankets in cold weather.

Concrete in Cold Weather

Below 5°C, cement hydration slows significantly and concrete gains strength slowly. Below 2°C, hydration may effectively stop. Fresh concrete must not be allowed to freeze before reaching a minimum strength of approximately 5 N/mm². Cold-weather concreting measures include: heating mixing water; using accelerating admixtures; using rapid-hardening cement (RHPC); insulating formwork; and providing heated enclosures. Do not use calcium chloride accelerators in RC (causes reinforcement corrosion).

Chloride Content Limits (EC2)

EC2 and BS EN 206 limit the total chloride content of concrete to protect embedded reinforcement from chloride-induced corrosion. For reinforced concrete: maximum 0.40% Cl⁻ by mass of cement. For prestressed concrete: maximum 0.20%. For unreinforced concrete: maximum 1.00%. All constituent materials (cement, aggregates, admixtures, mixing water) must be tested and their chloride contributions summed. Sea-dredged aggregates require chloride washing before use in RC.

Frequently Asked Questions – Concrete Mix Design BS 8500 / EC2 UK 2026

What is BS 8500 and how does it relate to BS EN 206?

BS EN 206:2013+A2:2021 is the European harmonised standard for concrete specification, published in the UK by BSI. It sets the general framework for classifying concrete by strength, exposure class, consistency, and maximum aggregate size. BS 8500 is the UK complementary standard that supplements BS EN 206 with UK-specific requirements — most importantly, the designated mix system (GEN, RC, PAV, FND series) in BS 8500-2, and the exposure class limiting values table (Table A.1) in BS 8500-1 that specifies the maximum w/c ratio, minimum cement content, and minimum strength class for each exposure class. In UK practice, concrete specifications must comply with both BS EN 206 and BS 8500 simultaneously. Neither standard alone is sufficient.

What is the difference between a designated mix and a designed mix?

A designated mix (e.g. RC30, GEN1, PAV1) is a pre-defined concrete mix whose composition is fixed in BS 8500-2. The specifier simply names the mix and the concrete producer guarantees it meets the BS 8500-2 specification — no further mix design work is needed by the specifier. Designated mixes cover most standard domestic and light commercial applications. A designed mix specifies performance requirements — strength class, exposure class, maximum w/c ratio, minimum cement content — and requires the producer to design and demonstrate compliance with a specific mix. Designed mixes are necessary for demanding structural applications not covered by the designated mix system, or where the engineer needs to specify particular performance properties (e.g. low heat of hydration, self-compacting, specific aggregate type).

How do I determine the exposure class for my concrete?

Exposure class selection is the most important step in concrete specification and should be done by the structural engineer or specifier based on the intended environment of the concrete element. The process is: (1) Identify all relevant deterioration mechanisms the concrete will be exposed to — carbonation, chlorides, freeze-thaw, chemical attack. (2) Assign an exposure class from each relevant family (XC, XD, XS, XF, XA) — most elements have at least one class from XC and possibly others. (3) Use the most onerous class in each family to determine the limiting values. For a UK house foundation in normal ground with no chloride risk and no freeze-thaw at foundation level, XC2 is typically the governing class. For an external ground floor slab in frost areas, both XC4 and XF1 apply simultaneously — use the more onerous limits from each.

What is the minimum concrete strength for reinforced concrete in the UK?

Under Eurocode 2 and BS 8500, there is no single minimum strength for all reinforced concrete — the minimum depends on the exposure class. For the most benign RC environment (XC1 — dry internal), the minimum strength class is C20/25 (characteristic cylinder/cube strength). For exposed external RC (XC4), the minimum is C30/37. For RC in de-icing salt environments (XD3), the minimum is C40/50. In UK domestic construction, C30/37 (RC30) is the most commonly specified strength class for general external RC work, as it satisfies both XC3/XC4 durability requirements and most structural design requirements for beams and slabs.

How is concrete cover to reinforcement calculated under EC2?

Nominal cover to reinforcement under EC2 is calculated as: cnom = cmin + Δcdev, where cmin is the minimum cover determined from the exposure class and bond requirements, and Δcdev is the construction tolerance allowance (typically 10mm for normal site conditions, reduced to 5mm for precast with special quality control). The minimum cover cmin is the greater of: (a) the minimum cover for the relevant exposure class from BS 8500-1 Table A.1 (adjusted for structural class); (b) the minimum cover for bond (typically the bar diameter or 10mm); and (c) any minimum for fire resistance from BS EN 1992-1-2. For a standard RC ground floor beam in XC4 exposure, Structural Class S4: cmin = 30mm (from Table A.1) + 10mm (Δcdev) = 40mm nominal cover.

What concrete mix should I specify for a house foundation?

For a typical domestic strip or trench fill foundation in the UK on normal ground (no sulphate risk): the governing exposure class is XC2 (wet, rarely dry — buried concrete). This requires a minimum strength class of C25/30, maximum w/c ratio of 0.65, and minimum cement content of 280 kg/m³. The BS 8500 designated mix equivalent is RC25 or, where the engineer permits use of the lower designation system, FND2 if sulphates are present. For most domestic projects, GEN1 (C15/20) is widely used for strip foundations as a pragmatic specification under the designated mix system — it slightly relaxes the XC2 limiting values but is accepted by Building Control for standard domestic foundations. If a structural engineer is involved and specifying to BS 8500-1 Table A.1, the correct minimum is RC25 for XC2 exposure.

What is the structural class and how does it affect cover?

Structural class is a concept in EC2 that links the required concrete cover to the design life of the structure and the concrete strength — recognising that higher-strength, denser concrete requires less cover to achieve equivalent durability. EC2 defines Structural Class S1–S6, with S4 as the default for a 50-year design life. The structural class can be reduced by 1 (reducing required cover by 5mm) if the concrete strength is increased by one grade above the minimum for the exposure class, if the element is a slab, or if the design life is reduced below 50 years. Conversely, structural class increases to S6 for 100-year design life structures. The adjustment is made to cmin, and Δcdev (typically 10mm) is always added on top to give cnom.

When should I use sulphate-resisting cement (SRPC)?

Sulphate-resisting Portland cement (SRPC) should be used whenever concrete will be in contact with soils or groundwater containing significant sulphate concentrations. BS 8500-1 classifies sulphate risk using the DS (Design Sulphate) class system — DS-1 to DS-5. SRPC (or combinations such as CEM I + GGBS) is required from DS-2 upwards. In practice, a ground investigation and soil/water chemistry testing should be carried out before specifying any below-ground concrete. In the absence of ground investigation data on brownfield, clay, or contaminated sites, a precautionary DS-2 or DS-3 classification with SRPC mortar should be assumed. The additional cost of SRPC over standard CEM I cement is typically 10–20%.

How do I specify concrete for a driveway or car park slab?

A concrete driveway or residential car park slab is subject to multiple exposure classes simultaneously: XC4 (cyclic wet/dry carbonation); XF4 (freeze-thaw with de-icing salts — if de-icing salts are used or likely); and potentially XD3 (chloride from de-icing salts — for car park decks). The BS 8500 designated mix for residential driveways is PAV1 (C30/37, air-entrained, maximum w/c 0.55, minimum cement 340 kg/m³). For a domestic driveway, RC30 without air entrainment is sometimes used, but PAV1 is the correct specification for frost-exposed trafficked slabs. For multi-storey car park decks subject to XD3 exposure, a designed mix of at least C40/50 with a maximum w/c of 0.45 is required.

What does the strength class notation C30/37 mean?

The strength class notation C30/37 refers to the characteristic compressive strength of the concrete at 28 days. The first number (30) is the characteristic cylinder compressive strength fck measured on 150mm diameter × 300mm cylinders to BS EN 12390-3, in N/mm² (megapascals). The second number (37) is the characteristic cube compressive strength fck,cube measured on 150mm cubes to BS EN 12390-3. The cube strength is approximately 25% higher than the cylinder strength due to the end restraint provided by the testing machine platens. Eurocode 2 structural design uses the cylinder strength in calculations; UK conformity testing uses cube specimens. When someone says they are ordering "C30 concrete" or "37N concrete" in the UK, they are referring to the same C30/37 strength class.

How does using GGBS or fly ash affect the mix design?

Using supplementary cementitious materials (SCMs) such as GGBS (ground granulated blast-furnace slag) or fly ash (PFA) as partial replacements for Portland cement affects the mix design in several ways. Both materials react more slowly than CEM I — early-age strength (1–3 days) is lower but 28-day and longer-term strength is equivalent or better. Key effects include: reduced heat of hydration (important for mass concrete and avoiding thermal cracking); improved chloride and sulphate resistance (denser pore structure at equivalent or lower w/c); and reduced carbon footprint (GGBS and PFA are industrial by-products with much lower embodied carbon than CEM I). BS 8500-1 allows up to 50% GGBS or 35% fly ash by mass of total binder, with the SCM content above 25% receiving a k-value credit that effectively allows a slightly higher total w/c ratio for equivalent durability. GGBS concretes require extended curing at low temperatures.

What is the difference between prescribed, designed, standardised, and proprietary concrete mixes?

BS EN 206 and BS 8500 define four concrete specification methods. A designed mix (described above) specifies performance; the producer designs the proportions. A prescribed mix specifies the proportions directly (e.g. 1:2:4 by volume) — the specifier takes responsibility for the performance. A standardised prescribed mix is a prescribed mix whose proportions and constituent materials are fixed in a published standard (BS 8500-2 Table 1). A designated mix (GEN1, RC30 etc.) is a standardised prescribed mix given a trade name. In practice, designated mixes dominate domestic and light commercial work in the UK; designed mixes dominate all engineered structural concrete. Prescribed mixes (specifying proportions directly) are used for small site-mixed volumes but carry the risk of performance inconsistency.